Description and Specification for Lab Tenders
Astra Scientific Computerized Cascade Refrigeration Trainer.
The cascade Refrigeration systems with two-stage compression are used
for the generation of particularly low temperatures. At very low
temperatures large pressure differences are required between the
evaporator and condenser. In a compressor the volumetric efficiency
drops significantly at high-pressure ratios.
Therefore, two compressors are connected in series, with each compressor
only having a relatively low-pressure ratio. This makes a more
favorable dimensioning of the low-pressure stage compressor possible.
Due to the large specific volume it requires a larger capacity at lower
drive power.
In addition, intercooling between the low-pressure compressor (LP) and
the high-pressure compressor (HP) reduces the outlet temperature of the
HP compressor to harmless values and improves the efficiency of the
compression.
All relevant measured values are recorded by sensors and displayed. The
simultaneous transmission of the measurements to the software enables
analysis and the representation of the process in the log p-h diagram in
real time. Additionally, two flow meters indicate the total volumetric
flow rate and the volumetric flow rate in the intercooling.
FEATURES:
• Design and function of a refrigeration system with two-stage compression and injection intercooling
• Effect of the inlet temperature at the HP compressor on the efficiency of the compression
o With intercooling
o Without intercooling
• Effect of the additional refrigerant intercooling
• Distribution of the compressor pressure ratios
• Represent and understand the refrigeration cycle process in the log p-h diagram
SPECIFICATION:
• Low-pressure compressor (LP)
Displaced volume: 25,93cm3
Power consumption: 550W
Refrigeration capacity: 1744W at -10/32°C
• High pressure compressor (HP)
Displaced volume: 8,86cm3
Power consumption: approx. 275W
Refrigeration capacity: 583W at -10/32°C
• Refrigerant
Filling volume: 1,29kg
CO2-equivalent: 1,8t
• Measuring ranges
flow rate: 2…29L/h, 4…40L/h
Pressure: 1x -1…15bar, 2x -1…24bar
Temperature: 8x -75…125°C
Power:
0…562W (heater)
0…750W (LP compressor)
0…2250W (HP compressor)
• Required for operation
230V, 50Hz, 1 phase
230V, 60Hz, 1 phase